← BACKSolarIQDEMOREAL DATA
Area Science Park PV Q2 · 14 kWp · 3 inverters · 8 strings · real SCADA data · 2013-01-012021-11-16
PLANT PERFORMANCE
98.5%
fleet string conformance · target ≥ 95%
DATA INTEGRITY
98.7%
INV-02 voltage channel fault (2021)
ANOMALOUS ENERGY
4.9 MWh
string fault 1.7 + DAQ gap 3.2 · 2013–21
FAULT STRINGS
1 / 8
string 3 open-circuit (2017)
STRING CONFORMANCE — INVERTERS × STRINGS · click row for diagnosis≥98 96–98 <96
INV-01
INV-02
INV-03
AI DIAGNOSIS — INV-02CRITICAL
INV-02 · DC voltage channel fault (2021)
DC voltage reads 0 from 2021-05-28 to 2021-11-15 (973 h) while string currents track normally — a DAQ/voltage-channel fault, not an outage; ≈3.2 MWh of output is invisible in the V×I power record (the 2021 efficiency step-down).
Recommended action
Verify the INV-02 DC-voltage transducer and wiring; re-integrate string-current-derived power into the record.
GENERATION vs POTENTIAL (kW) · 2021-06-16 · 24h — actual is missing the INV-02 voltage-channel output
LOSS ATTRIBUTION (MWh · 2013–21)
Real SCADA data — Area Science Park PV plant Q2, Trieste, Italy (CC-BY-4.0) · SolarIQ integrates with your existing plant data systems through the protocol gateway